Estimate how much air a commercial kitchen hood needs to exhaust based on its style (wall canopy, island, backshelf), its length and the heaviest appliance under it — plus a starting point for makeup air and duct size.
Exhaust CFM = CFM per linear foot × hood length (× 2 for double island) Hood length ≥ appliance line + 6 in. at each end Makeup air ≈ 85% of exhaust Duct area = CFM ÷ 1,800 fpm → round diameter
CFM per foot for unlisted Type I hoods (IMC 2009 §507.13): wall canopy 200 / 300 / 400 / 550 for light, medium, heavy and extra-heavy duty; single island 400 / 500 / 600 / 700; double island 250 / 300 / 400 / 550 per side; backshelf 250 / 300 / 400; eyebrow 250 for light and medium only. Makeup air is commonly designed at about 80–90% of exhaust so the kitchen stays slightly negative. Grease ducts typically run at 1,500–2,500 fpm; 1,800 fpm is used here.
A burger restaurant with a gas charbroiler, two fryers and a griddle in a 12 ft line under a 13 ft wall-mounted canopy hood.
The heaviest appliance sets the duty for the whole hood: a single charbroiler in a line of ovens makes it a heavy-duty hood. Island hoods need more air than wall hoods because there is no wall to contain the plume, and cross-drafts pull smoke away more easily.
Most commercial hoods sold today are listed (UL 710) and tested to capture at lower airflow than the prescriptive table. The manufacturer’s listing, not this table, will usually set the final CFM — often saving on fan energy and makeup air heating.
Kitchen ventilation is a life-safety system. Final design, including fire suppression, grease duct construction, clearances and makeup air, must follow the codes adopted locally and be confirmed by the hood manufacturer, a qualified engineer and the authority having jurisdiction.
Under the older prescriptive IMC table, a wall canopy needs 200–550 CFM per foot depending on appliance duty, and a single island canopy 400–700. Listed hoods often run lower.
Usually close to the exhaust volume — commonly 80–90% delivered through the hood or HVAC, with the building balanced so the kitchen stays slightly negative.
Fryers, griddles and open-burner ranges are typically classed as medium duty. Gas charbroilers and woks are heavy duty; solid-fuel appliances are extra heavy.
No. It is a planning estimate. Permit design must follow local codes and the hood’s listing.